•  Press the “MENU” button momentarily to select the parameter to be changed. 
•  Press the Up/Down arrow keys to adjust the parameter value. 
•  If there is more than one value for any given parameter the MENU key will scroll from the first value to 

the next value and then on to the next parameter. 

•  Holding the Up/Down arrow keys will cause the value to increment faster. 
•  The display will return to the primary screen after eight seconds if no keys are depressed. 

 

2.3.1 SET TEMPERATURE 
 

Values: ‐20.0 °C to +199.0 °C, or as defined by the limits set by CONTROL RANGE 

 

Default value = 25.0 °C 
 
Description:  SET TEMPERATURE is the control temperature that the controller tries to maintain. Note that 
controller set point should not be set outside the range suitable for the temperature sensor. Consult TE 
Technology for customization if you need a thermistor that can provide a different control range. Also, be 
sure that the set point is also appropriate to the TE device. 

 
2.3.2 PROPORTIONAL BW 
 

Values:  0.5 °C to 100.0 °C 

 

Default value = 5.0 °C 

 

Description: The proportional bandwidth is the temperature span over which the power is proportioned 
from  100%  to  0%  power,  centered  about  the  temperature  set  point.    That  is,  the  controller  output 
decreases  to  50%  power  as  it  reaches  the  set  point  and  to  0%  as  it  reaches  the  end  of  the  bandwidth 
range below the set point (when in the cooling mode). 
 
For example, suppose the controller is being operated in the cooling mode, the set point is 10.0 °C, and 
the  bandwidth  is  set  to  5  °C.    The  controller  power  starts  to  proportionally  decrease  as  the  sensor 
temperature cools below 12.5°C.  The power will be reduced to 50% when the sensor is at 10.0 °C.  Finally, 
the  power  will  be  at  0%  when  the  sensor  is  at  7.5°C.    (Of  course,  this  example  presumes  that  the 
INTEGRAL GAIN and DERIVATIVE GAIN are set to 0 and that the cooler would have enough capacity to cool 
to 7.5 °C.) 
 
If the bandwidth is set too narrow, the temperature will oscillate around the set point.  If the bandwidth is 
too wide, the controller will be slow to respond or may never reach set point. 
 

2.3.3 INTEGRAL GAIN 
 

Values: 0.00 to 10.00 (repeats per minute) 
Default value = 1.00 
 
Description:  This  corrects  for  any  offset  between  the  set  temperature  and  the  sense  temperature  by 
averaging the offset with respect to time.  This essentially shifts the proportional bandwidth. 
 
For  example,  suppose  the  set  temperature  is  10.0  °C,  the  bandwidth  is  set  to  5  °C,  and  the  controller 
settled to a constant 11.2 °C (corresponding to 74% power).  If the integral control is then set to 1 repeat 
per minute, the controller will increase the power to 98% in 1 minute, providing extra cooling to move the 
temperature closer to the set temperature.  In this example, after one minute of operation the controller 
calculated that the difference between the desired set temperature and the actual temperature was +1.2 
°C.  With a bandwidth of 5 °C, the controller uses the INTEGRAL GAIN to add an additional 24% output per 
minute (100% output / 5 °C * 1.2 °C = 24 %).  This additional 24% output was added to the existing 74% 
output  to yield  98%  output.    The  integral portion  of  the  output  is  continuously  recalculated  at  the  rate 
specified  by  the  integral  gain  setting.    The  INTEGRAL  GAIN  always  adds  or  subtracts  from  the  present 
output power.  Of course, the maximum output is limited to 100% and the minimum is limited to 0%. 
 
If the integral control is set too high, the temperature will oscillate.  If integral control is set too low, it will 
take a long time for the temperature to settle to steady state. 