12-Station Controllers

VacTrac™ Conveying Systems

6-2 Operation States

OFFLINE

The

OFFLINE

operation state is the default state at the point

when you apply power to the controller. While in this state, all
outputs in the system are deactivated and access to the menu
system is permitted. All station demands are ignored.

IDLE

(Startup)

If you press the

START/STOP

key in the

OFFLINE

state, the

controller enters the

IDLE

(Startup) state. If no demand is on the

system, the controller immediately enters the

READY

state. With a

valid demand, the

IDLE

(Startup) state allows the pump to get up

to speed before starting to load a station.

While in the

IDLE

(Startup) state, all station sequence valves are

closed and the vent valve is open. The vent valve allows the
vacuum pump to vent to atmosphere, keeping the system from
becoming depressurized.

LOADING

Following the

IDLE

(Startup) state, the vent valve is closed and

the first station in demand loads when that station sequence valve
opens. This is the

LOADING

state. You can define load times for

each station. The controller loads the station in demand until one of
two events occur:

• The volume fill sensor becomes active.

- or -

• The load time is exhausted.

At the end of the

LOADING

cycle, the controller closes the

sequence valve and continues to the next station in the queue. If all
stations are satisfied, the controller enters the

IDLE

(No Activity)

state.