Warnings

Table 6-3 is a list of diagnostic messages that may be displayed on the
Integral Display, on the Model 375 Field Communicator or by the Radar
Configuration Tools (RCT) software. Warnings are less serious than errors
and in most cases do not result in Analog Output alarms.

Warnings are indicated by a message at the bottom of the RCT workspace. To
see the warning message do one of the following:

Click the Read Gauge Status icon

in the toolbar at the top of the

RCT workspace.

1. Open the Advanced section in the RCT workspace Project Bar and
click the Device Commands icon,
or
choose the Device Commands option from the View menu.
2. Open the folder named Diag and double-click the Read Gauge
Status option.

Table 6-3. Warning messages.

Message

Description

Action

Reference pulse not
found.

Possible cause:

• Reference pulse immersed in

high dielectric liquid.

• Wrong threshold level T1.
• Hardware error.

• View the waveform plot and check

amplitude threshold T1.

• Check that the tank is not overfull.

No level pulse is
found.

Possible cause:

• Wrong threshold level T2.
• Liquid level in Dead Zone or

below probe end.

• View the waveform plot and

check amplitude threshold T2.

Interface pulse not
found.

Possible cause:

• Wrong threshold level T3.
• Interface level too close to the

upper product level.

• No level pulse detected.

• View the waveform plot and

check amplitude threshold T3.

Internal temperature
out of range.

-40 ºC<Internal Temperature<85 ºC.

Contact Rosemount service
department.

Volume computation
warning.

• Volume configuration error.
• Strapping table error.

• Check that correct tank type is

selected for volume configuration.

• Check that tank dimensions for

volume are correct.

• If strapping table is used, check the

level vs. volume points.

Immersed probe.

• Wrong threshold level T4.
• Reference pulse immersed in

liquid.

• View the waveform plot and check

amplitude threshold T4.