Rosemount 3300 series, Reference manual – Emerson Guided Wave Radar Level and Interface Transmitters 3300 User Manual

Page 92

Advertising
background image

Reference Manual

00809-0100-4811, Rev CA

February 2006

Rosemount 3300 Series

6-12

To set the Upper Null Zone do one of the following:

1. Select the HART command [1, 3, 3, 1].

2. Enter the desired value,

or

1. Start the Radar Configuration Tool (RCT).

2. Click the Setup icon in the RCT workspace Project Bar.

3. Choose the Tank Config tab in the Setup window.

4. Click the Receive Page button.

5. Type the desired value in the Upper Null Zone field.

6. Click the Send Page button. Now the Upper Null Zone is stored in the

transmitter memory.

Figure 6-8. Upper Null Zone

Figure 6-9. Identifying the Upper
Null Zone in the RCT Waveform
Plot

Reference Gauge Height

Upper Null
Zone

Product Level

Upper Reference Point

UPPE

RNU

L

L

ZONE

Upper Null Zone

Disturbance

W

AVE

FORMPLO

T

_UNZ