VOLUME
CONFIGURATION

Transmitter Variables

Select the Volume option in order to configure the transmitter for volume
measurements.

Volume Units

Choose one of the following units:

Gallons

Liters

Imperial Gallons

Cubic Meters

Barrels

Cubic Yards

Cubic Feet

Cubic Inch

Tank Type

Choose a standard tank shape, or select the strapping option. Standard
shapes are: Vertical Cylinder, Horizontal Cylinder, Vertical Bullet, Horizontal
Bullet or Sphere. (If Primary Variable is Level choose None for Tank Type).

If your tank does not correspond to any of the above tank shapes, select Strap
Table.

Tank Dimensions

If a standard tank type was chosen, enter the diameter and height of the tank.
See “Volume Configuration” on page 4-5 for information on how to specify
tank dimensions.

Strapping Table

If tank type Strapping Table was chosen, enter how many entries you will use
and the actual level and volume points. You can enter from 2 to 10 points. The
strapping points must be entered such that the first point corresponds to the
lowest level, and the last point corresponds to the topmost level of the tank.

HART Comm

1, 1, 1, 1

HART Comm

1, 3, 1, 2

HART Comm

1, 4, 3, 1

HART Comm

1, 4, 3, 2-3