When calibrating the transmitter it is important that the product surface is calm
and that the tank is not being filled or emptied.

A complete calibration is performed in two steps:

1. Calibrate the Distance measurement by adjusting the Calibration Offset

parameter.

2. Calibrate the Level measurement by adjusting the Reference Gauge

Height.

Distance calibration

1. Measure the actual distance between the Upper Reference Point and the

product surface.

2. Adjust the Calibration Offset so that the Distance measured by the

transmitter corresponds to the actual distance.
The Calibration Offset parameter is available via
HART command [1, 4, 5, 5],
or
RCT: open the Advanced section in the Project Bar and choose Device
Commands>Basics>Set Calibration Offset.

Level calibration

1. Measure the actual Product Level.

2. Adjust the Reference Gauge Height so that the measured Product Level

corresponds with the actual level.

Figure 6-7. Distance and Level
calibration