Rosemount 3300 Series

3-22

Power Requirements

Terminals in the transmitter housing provide connections for signal cables.

The 3300 transmitter is loop-powered and operates with power supplies
ranging from 11 to 42 VDC. For Intrinsically Safe output the supply voltage
must be within 11 to 30 VDC. For Explosion-proof/Flame-proof the supply
voltage must be within 16 to 42 VDC.

Maximum Loop
Resistance

The maximum current loop resistance can be gained from the following
diagrams:

Figure 3-12. Explosion-proof
/Flame-proof installations

Figure 3-13. Non-hazardous
installations

Figure 3-14. Intrinsically Safe
installations

MA

X_

LO

A

D

_

E

X

NOTE
This diagram is only valid if the
load resistance is at the + side,
otherwise the maximum load
resistance is limited to 300 Ohm.