Setup - volume, Setup - volume -22, Rosemount 3300 series – Emerson Guided Wave Radar Level and Interface Transmitters 3300 User Manual

Page 74: Reference manual

Advertising
background image

Reference Manual

00809-0100-4811, Rev CA

February 2006

Rosemount 3300 Series

4-22

Measurements Below Probe End

The Present Level=0... check box controls how the level value is presented
when the tank is almost empty. By selecting this check box the Level is set
equal to zero as long as the product surface is below the probe.

If the check box is not selected, the Level value is equal to the difference
between Reference Gauge Height R and Probe Length L when the product
surface is below the probe (see “Basic Configuration” on page 4-2 for
information on tank geometry).

Setup - Volume

The Volume tab lets you configure the transmitter for volume calculations.

Figure 4-17. Setup Volume tab

You can choose one of the standard tank shapes or the strapping option.
Choose None if volume calculation is not used at all.

Choose one of the following options:

Vertical Cylinder

Horizontal Cylinder

Vertical Bullet

Horizontal Bullet

Sphere

Strap table

None

See Section 4: Volume Configuration for more information on Volume
configuration.

Level=0

Level=R-L

L

E

VE

L

B

EL

O

W

PR

O

B

E.

EP

S

RCT

-S

ETUP VOL

U