4 administration, 5 network, 6 environment sensor – Eaton Electrical 34003991EN/EB User Manual

Page 11: 1 list of ports used

Advertising
background image

Network Management Card

– User Manual

34003991EN/EB

Page

11/118

1.3.4 Administration

Up to 35 workstations(in TCP connected mode) or up to 100(in UDP broadcasted mode) protected by Network

Shutdown Modules - Central or local configuration.

Up to 5 browsers connected at the same time (3 in SSL).

Minimum recommended browser versions: Internet Explorer 6.x / 7.0, Mozilla Firefox 1.5 / 2.0 / 3.0

E-mail sending configurable according to UPS alarms and transmission of a periodical report.

Control of UPS on/off switching via the HTML interface.

Adjustment and control of PowerShare outlets via the HTML interface, sequential starting of the installation and

optimisation of backup time by shutting down non-priority systems.

Automatic data and time adjustment via NTP server.

Protection by encrypted password.

Protection by secure SSL connection.

Saving of logs in the non-volatile memory.

Languages available: English/French/Spanish/German/Italian.

On-line help in English available for each page.

Card firmware updated via the network.

Card Mass settings via the network with the NMC tool.

1.3.5 Network

Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet.

1.3.5.1 List of ports used

BootP, DHCP

UDP 68, 67

HTML

TCP 80

SSL

TCP 443

NSM in connected mode

TCP 5000

NSM in broadcasted

UDP 4679 and 4680

SMTP

25

NTP

123

SNMP V1

161

TRAP SNMP

162

1.3.6 Environment sensor

Temperature measurement from 0 to 70 °C with +/- 1 °C accuracy.

Measurement of humidity from 0 to 100 % with +/- 6 % accuracy.

Min / max time-stamped function for temperature and humidity.

Choice of temperature readings in Celsius or Fahrenheit.

High and low thresholds, hysteresis and offset adjustable via Web interface.

Possibility of notification of status changes by e-mail, SMS or SNMP trap.

Position detection of 2 dry contacts (maximum sensor/contact distance: 20 m).

Name and status of each configurable contact.