Network Management Cards are compatible with the "Enterprise Power Management" supervision system, with the

MGE Office Protection Systems network protection system and with Powerware Netwatch.

Network Shutdown Module

Enterprise Power Manager

Management-Pac 2

1.2.2 Direct sending of E-mail

When a UPS event occurs, the Network Management Card can directly notify up to 4 intranet or extranet addresses

by e-mail. (see E-mail Notification and

E-mail message settings

)

1.2.3 Sending text messages (SMS)

The card offers the possibility of redirecting UPS alarms to an e-mail server. The format of these e-mails is compatible

with mobile telephone e-mail/SMS transfer systems proposed by ISPs. The format to be used depends on the service

provider.

For example, [email protected] (text messages).

1.2.4 Compatibility with the Network Management Systems (NMS) – Trap

sending

The Network Management Cards are compatible with the major Network Management Systems (IBM Tivoli, CA

Unicenter, HP Insight Manager). The Management-Pac 2 offering includes the necessary SNMP plug-ins to allow an

easy integration in the NMS. Events are notified by SNMP trap.

NMS can subscribe on page

Notified Applications

The trap list is given in the

appendix

.

1.2.5 Environment Sensor (option)

The

Environment Sensor

(66846) solution comprises a box to be connected to the Card Settings port of the

Network Management Cards.

Environment Sensor enables measurement of temperature and humidity around the UPS, consideration of external

alarms via 2 dry contacts and notification of alarms according to pre-programmed thresholds. (see

Environmen

Status

and

Environment Configuration

)