Eaton Electrical 34003991EN/EB User Manual

Page 115

Advertising
background image

Network Management Card

– User Manual

34003991EN/EB

Page

115/118

8.2.2 Table des TRAPS : (1.3.6.1.4.1.705.1.11)

SNMP traps are sent when alarms appears and desappears.

Level : 1:informational , 2:major, 3:critical

MIB TRAP

Trap #

Level

-upsmgBatteryFault

Trap 1

Level 3

-upsmgBatteryOK

Trap 2

Level 1

-upsmgAtLowBattery

Trap 5

Level 3

-upsmgFromLowBattery

Trap 6

Level 1

-upsmgChargerFault

Trap 7

Level 3

-upsmgChargerOK

Trap 8

Level 1

-upsmgOnBattery

Trap 11

Level 2

-upsmgReturnFromBattery

Trap 12

Level 1

-upsmgOnByPass

Trap 13

Level 2

-upsmgReturnFromByPass

Trap 14

Level 1

-upsmgUtilityFailure

Trap 17

Level 2

-upsmgUtilityRestored

Trap 18

Level 1

-upsmgOverLoad

Trap 21

Level 3

-upsmgLoadOK

Trap 22

Level 1

-upsmgOverTemperature

Trap 23

Level 3

-upsmgTemperatureOK

Trap 24

Level 1

-upsmgOffToStart

Trap 29

Level 2

-upsmgOffInProgress

Trap 31

Level 3

-upsmgCommunicationFailure

Trap 37

Level 3

-upsmgCommunicationRestored

Trap 38

Level 1

-upsmgRedundancyLost

Trap 65

Level 2

-upsmgRedundancyOK

Trap 66

Level 2

-upsmgProtectionLost

Trap 67

Level 2

-upsmgProtectionOK

Trap 68

Level 2

If the Environment Sensor is detected , the following information are managed.:

- upsEnvironmentComFailure

Trap 53

Level 2

- upsEnvironmentComOK

Trap 54

Level 2

- upsEnvironmentTemperatureLow

Trap 55

Level 2

- upsEnvironmentTemperatureHigh

Trap 56

Level 2

- upsEnvironmentTemperatureOK

Trap 57

Level 2

- upsEnvironmentHumidityLow

Trap 58

Level 2

- upsEnvironmentHumidityHigh

Trap 59

Level 2

- upsEnvironmentHumidityOK

Trap 60

Level 2

- upsEnvironmentInput1Closed

Trap 61

Level 2

Advertising