5 server protection, 1 set-up of the shutdown parameters – Eaton Electrical 34003991EN/EB User Manual

Page 65

Advertising
background image

Network Management Card

– User Manual

34003991EN/EB

Page

65/118

5 Server protection

5.1 Set-up of the shutdown parameters

The protection application : Network Shutdown Module or Netwatch, on protected server boot, subscribes itself

automatically to

notified applications

list and sends its essential data:

IP Address or hostname of the server on which it is installed: So that the card can inform it of power events.

Time required to shutdown the server (Shutdown Duration, configurable in the "Set-up" menu of each NSM): The

card takes into account the longest shutdown time of all the Network Shutdown Modules subscribed (This is the

Shutdown duration of the

Shutdown parameters

) page to manage UPS shutdowns without affecting any of

Shutdown Modules connected.

During normal operation, the protection application periodically checks its connection with the card.

In case of a major power event, the card sends information to the protection application which reacts according to the

situation. (shutdown order, programmed actions, messages to the administrator and to users via the network)

When the server shuts down, the protection application unsubscribes itself from the

notified applications

.

5.1.1 Shutdown criteria managed by the Network Management Card

During an extended power failure, three criteria may cause the server shutdown procedure to be initiated. If several

criteria are selected, (See page

Shutdown parameters

), the first criterion encountered will launch the shutdown

procedure.

At the end of the shutdown procedure, when all servers have been shut down, the UPS may shut down to avoid

unnecessary discharge of its batteries, depending on its configuration.