4.2.1.2 "UPS status" zone: Essential information

"Active sources": (available on parallel or modular UPS)

x UPS + y UPS redundant :

x indicates the minimal number of UPS necessary to power the load,

y indicates the number of UPS in redundancy.

An alarm can be generated if the number of UPS in redundancy is less than a configurable threshold. See UPS

modules section.

"Power source": indicates whether the power comes from the utility or from the UPS battery

"Output load level": indicates the power percentage used at UPS output

"Output": indicates if the different UPS outputs are protected.

"Master": indicates if the UPS main output is protected

"Group1 and Group2": indicates if the controlled outlets (if available) are powered.

The various icons showing the status of the UPS outputs are:

(green outlet)

Outlet powered

(red outlet)

Outlet not powered or not

protected

Battery Information :

"Battery load level": remaining battery charge (in percent).

The information is completed with the two following labels:

“Charging” : if the utility power is present and the battery charge is in progress

“Discharging”: if the UPS operates on battery.

“Fault”: if the battery is faulty.

"Remaining backup time": Estimation of the battery's maximum backup time remaining before UPS shutdown

"Battery status": Result of the last automatic battery test carried out by the UPS

Possible values are:

– OK: the test was completed correctly

– NOK: the battery needs to be checked

– Deactivated: the automatic battery test is not validated on the UPS