2 rs485 link configuration and connection, 1 rs485 connection – Eaton Electrical 34003991EN/EB User Manual

Page 80

Advertising
background image

Network Management Card

– User Manual

34003991EN/EB

Page

80/118

7.2.2 RS485 link configuration and connection

7.2.2.1 RS485 connection

The EIA RS485 link, 2 wires or 4 wires, must be polarized at a unique point of the link and must be adapted at both

ends for a good working.

Normally, the master of the network sets the polarity of the line. The INMC card is a slave equipment and don’t have

polarisation resistor.

The two ends of the line must be terminated. Allow for 1 or 2 terminators to avoid mismatching the line when any

equipment at the end of the line is disconnected.

The next figure gives the detail of the RS485 connector and the internals drivers:

Pin number

Function

1

R- : Receiver - (input)

2

R+ : Receiver + (input)

3

T- : Transmitter - (output)

4

T+ : Transmitter + (output)

5

0 V

Important notes:

Use twisted pair cable (cable specification 0.3mm

2

and capacitance 42pF/m)

The transmission range will increase if a cable with lower capacitance and larger diameter is used.

Use shielded cable in heavy industrial environments.