Eaton Electrical 34003991EN/EB User Manual

Page 39

Advertising
background image

Network Management Card

– User Manual

34003991EN/EB

Page

39/118

For the main outlet ("Master" by default)

The first shutdown criteria initiates the restart of the

shutdown sequence

.

If remaining time is under (0 to 99999 seconds, 180 by default) is the minimum remaining backup time from which

the shutdown sequence is launched.

If battery capacity is under (0 to 100%); this value cannot be less than that of the UPS and is the minimum

remaining battery capacity level from which the shutdown sequence is launched.

Shutdown after (0 to 99999 minutes, not validated by default) is the operating time in minutes left for users after a

switch to backup before starting the shutdown sequence.

Shutdown duration (120 seconds by default) is the time required for complete shutdown of systems when a switch

to backup time is long enough to trigger the shutdown sequences. It is calculated automatically at the maximum of

Shutdown duration of subscribed clients but can be modified in the Advanced mode.

If battery capacity exceeds Minimum battery level to reach before restarting the UPS after utility restoration

.

Important: Certain UPSs do not support this option

For the controlled outlets ("group 1 or group 2" by default)

The page enables programming of operation time and level in backup mode to manage outlet load shedding in the

event of electric power failure:

Switch Off after (from 0 to 99999, 65535 by default) defines the time during which the outlet is supplied starting

from the moment of utility failure. Caution, this time includes the outlet shutdown duration.

Switch Off if battery capacity under (0 by default) is an extra condition for outlet shutdown that can trigger the

shutdown sequence before the shutdown duration runs out.

Shutdown duration is the time required for complete shutdown of the systems supplied by the outlet when an

outlet shutdown sequence is launched.

It is calculated automatically using the maximum shutdown durations of notified applications on the outlets.

Switch On after (from 0 to 99999, default 65535) is the period between main output startup and startup of the

relevant programmable outlet, therefore outlet startup can be delayed in relation to the main output.

Important: Certain UPSs do not support this option

Security: The administrator has to click on Save and enter his/her login/password to save any modifications. The login

and password by default are: admin/admin