Eaton Electrical 34003991EN/EB User Manual

Page 53

Advertising
background image

Network Management Card

– User Manual

34003991EN/EB

Page

53/118

application) or Central (coming from the card).

The

Central shutdown configuration

is available by clicking on the Configuration link.

Shutdown duration: the shutdown duration necessary to properly shutdown the computer.

Shutdown after: the time available to the user from the power failure until the launch of the shutoff sequence of the

UPS and equipment This parameter is optional.

Many actions are available on this page:

Remove: Depending on the kind of application, the selected ones will definitively disappear from the table as SNMP

applications, or they will disappear and automatically re-subscribe as Network Shutdown Module applications.

Utility failure Test: Two alarms, 'Utility failure' and 'Utility restored' spaced 60 seconds apart, will be sent to the

applications selected, making sure that the applications can be reached over the network.

Shutdown Test: This test simulates a UPS on battery operation. It enables an easy check to see if the server

protection works correctly.

- No intervention on the UPS is required.

- The applications selected will process the simultaneous alarms and perform an actual shutdown sequence.

WARNING!

- This test will generate a REAL shutdown sequence of the selected servers on which the Network Shutdown Module

application is running.

Add NMS: allows an SNMP trap receiver to be added such as a Network Management System.

Modify NMS: allows an SNMP trap receiver to be modified.

Both buttons open a new window where it is possible to enter the Application name, the Hostname or IP Address, the

Trap community and the severity.

The default severity value is 1 – Warning