Network Management Card

– User Manual

34003991EN/EB

Page

35/118

UPS configuration may prevent the shutdown and restart commands from being properly run. Read the UPS user

manual for more information.

This page enables triggering of

startup and shutdown sequences

for the UPS main output and controlled outlets.

The status of each output is displayed by a symbol associated with the Off label (red symbol) or On (green

symbol).

The shutdown sequences take into account the time required for the registered servers to shut down without

losing data

(

see shutdown parameters

).

The main outlet has priority over the controlled outlets. Shutdown of the main outlet causes the controlled outlets

to shut down. Controlled outlets can only be started if the master outlet is on.

The Check column proposes six different commands, and a command is only actually started after clicking on

'Execute':

"Safe power down": A sequence to switch off output power is launched immediately. The systems supplied are shut

down correctly while the shutdown sequence is running, then the output is cut.

"Safe power down & reboot": A sequence to switch off then restore output power is launched immediately. The

powered systems are shut down correctly during the shutdown sequence, then the output is switched off.

Finally, the restart sequence is launched at the end of the time delay specified in the "Toggle duration" parameter. The

output status is updated.