6 measurements – Eaton Electrical 34003991EN/EB User Manual

Page 40

Advertising
background image

Network Management Card

– User Manual

34003991EN/EB

Page

40/118

4.2.6 Measurements

Click on "Measurements" in the menu

The next window shows the measurements for a mono phases UPS.

The following measurements are saved and time-stamped (env. 430):

"AC Normal : Voltage": Value of the utility voltage supplying the UPS

"AC Normal : Frequency": Value of the utility frequency supplying the UPS

"AC Output : Voltage": Value of the output voltage of your UPS

"AC Output : Frequency": Value of the output frequency of your UPS

"AC Output : Power (kVA)": Value of the output power of your UPS

"AC Output : Load level (%)": Value of the percentage of load at UPS output

"Battery : Capacity (%)": Percentage of charge available in the battery

"Battery : Remaining time (mn)": Estimation of the remaining backup time

The save frequency of these values is defined in the

"System"

page (60 seconds by default). Approximately 435

time-stamps are stored permanently on the card. The oldest time-stamps are automatically deleted.

"Save Log" enables all saved values to be opened or saved in CSV format. (compatible with Excel type

spreadsheets)

"Clear Log" enables deletion of all records. Enter the login/password to validate this action.

Advertising