2-15

MLC 104 Plus Series • Operation, Features, and Cabling

PRELIMINAR

Y

Using these pins and an external switch to trigger digital input

MLC104 DigInput-02

MLC 104 IP Plus

+12 V

Digital
Input

Normally
Open
Switch

GND

2k ohms

SW 2

+5.0 V

CTL

Digital input is triggered

by an external switch

wired between the I/O pin

and ground. The pull-up

resistor to +5.0 VDC is

activated (switch 2 is

enabled/closed).

Pin 1, 2, or 3 of the
Digital I/O Port

Digital I/O Port GND

Using a motorized surface access enclosure to trigger digital input

MLC104 DigInput-04

SW 1

MLC 104 IP Plus

HSA 822M/MS

+12 V

+12 V

Digital
Input

GND

Status
Pin

GND

2k ohms

SW 2

+5.0 V

CTL

CTL

Digital input at the MLC is triggered by a digital output from a motorized Extron

HSA 822M.
A closure to ground (switch 1) occurs when a certain condition is met on the HSA.

This closure to ground triggers the MLC.
The MLC must have the pull-up resistor to +5.0 VDC activated (switch 2 is

enabled/closed).

Pin 1, 2, or 3
of the Digital
I/O Port

Digital I/O Port

GND

See “Using Digital Inputs” in chapter 5, “Special Applications”, for a wiring

diagram for this example.