Isolated 4-20 mA Transmitter Output

CALIBRATION

Factory calibrated for 4-20 mA

SCALING RANGE 1.000 to 23.000 mA for any display range.

Reverse scaling allowed.

ACCURACY

± 0.1% F.S. ± 0.004 mA

TEMPERATURE
DRIFT

50 PPM/

C from 0 to 65C ambient

EXTERNAL LOOP
POWER SUPPLY

35 VDC maximum

OUTPUT LOOP
RESISTANCE

Power supply

Minimum

Maximum

24 VDC

10

 700

35 VDC (external)

100

 1200

DATA
SOURCE

Display Value, Maximum Display Value, Minimum Display
Value, or Modbus Register.

OVERRANGE

Programmable mA output for overrange condition.

UNDERRANGE

Programmable mA output for underrange condition.

COMMUNICA-
TIONS BREAK

Programmable mA output when a slave device does not
reply within the Slave Response Timeout (Available also in
Slave mode v1.1 & up).

MAXIMUM
OUTPUT

Programmable absolute maximum mA output desired.

MINIMUM
OUTPUT

Programmable absolute minimum mA output desired.