Setting the Relay Action

The relays Action menu allows the user to set up the operation of the
relays. The relays may be set up for any of the following modes of
operation:

1. Automatic reset (non-latching)
2. Automatic + manual reset at any time (non-latching)
3. Latching (manual reset only, at any time)
4. Latching with Clear (manual reset only after alarm condition

has cleared)

5. Pump alternation control (automatic reset only)
6. Off (relay and status LED disabled)

The following graphic shows the action menu for relay 1. Relays 2 to 4
are set up in a similar fashion.

Act 1

auto

A-nman

latCh

Lt-Clr

From Relay 1

Menu

altern

off

Press Enter/Ack to

Make Selections

Press Menu to

Exit at any Time

Press Up Arrow to

Scroll Through

Choices

Programming Set and Reset Points

High alarm indication: program set point above reset point.
Low alarm indication: program set point below reset point.
The deadband is determined by the difference between set and reset
points. Minimum deadband is one display count. If set and reset points
are programmed the same, relay will reset one count below set point.
The following graphic shows the Set/Reset point menu for relay 1. The
menu is similar for relays 2 to 4.

Set 1

Rset 1

Enter Set Point

Value

Enter Reset

Point Value

Quick Points

Press Up arrow and Menu
at the same time to access
set/reset points quickly.