Snooper Mode (Snoopr)
The Snooper mode is used to listen to data being transmitted on the
bus. Multiple Snoopers can be connected to the RS-485 bus and
display any process variable. The same process variable can be
displayed in multiple locations.

Press Enter/Ack to

Make Selections

Press Up Arrow to

Scroll Through Choices

Press Menu to Exit at

any Time

Press Right Arrow to display and
change the setting for the number of
digits used for the Register Number.

t-resp

t-poll

Enter Polling

Time Value

data.1

short

long

float

binary

bcd

unsigd

signed

1234

4321

2143

3412

The last two Byte-Order settings are not

available for Short Integer data types.

SLAv.1d

Enter Process

Variable Value

Snoopr

funCod

fun 03

fun 04

reg.nbr

Enter Register
Number Value

5 dig

6 dig

Notes:

1. To minimize the possibility of communication errors and

communication break conditions, use a poll time of 5 seconds or
more with slow baud rates (e.g. 4800 bps or less).

2. The poll time for meters set up for Snooper mode must be greater

than the Master’s poll time. This setting corresponds to the time
window during which the Snooper listens to the bus for a reply by
the slave device being polled by the master device. As soon as the
Snooper detects a new reply on the bus, the display is updated. If
there is no reply within the Poll Time setting, the Snooper goes into
communications break condition.

3. The Slave Response Timeout (t-resp) setting is not applicable to

the Snooper mode.