Analog Output Programming (aoutpr)
The 4-20 mA analog output can be programmed for its source of data,
overrange and underrange, absolute max and min output, and
communications break values. It can also be calibrated manually or
automatically.

Aoutpr

sourCe

O-rang

U-rang

break

nmax

Press Enter/Ack to

Make Selections

Press Up Arrow to

Scroll Through Choices

Press Menu to Exit at

any Time

disp

nmax

nmin

nmin

reg

Calib

nman

auto

4 nma

20 nma

Enter Actual
4 mA Value

Enter Actual

20 mA Value

Enter Over-range

Value

Enter Under-range

Value

Enter

Communication-

Break Value

Enter Minimum

Output Value

Enter Maximum

Output Value

*

Communication-Break menu
available only in Master Mode.

*

Factory Use

Only!


The overrange and underrange values are the values that will be
output when the display shows an overrange or underrange
condition.

The max and min values are the absolute limits for the 4-20 mA
output.

The communications break value determines the mA output when a
slave fails to reply to a command within the Response time.

For calibration instructions, see 4-20 mA Output Calibration,on
page 57.