6.2.2. Results of "MAN" mode

 At the end of the test if

the

insulation

resistance

is

lower

than R

MAX

(see Table2)

and the instrument
generates

the

Nominal test Voltage,
the instrument emits a
double

beep,

indicating the positive
outcome of the test

and displays a screen
similar to the screen to
the right.

M

05.06.01

Insulation Resistance

1.07

M

514V 15s

MAN 500V

Voltage during the Test

Duration of the Test

Test mode

Test voltage set

FUNC VNOM


In order to evaluate the test you must compare the result with the limits indicated in the
Guidelines (see Table1).

The displayed result can be stored pressing the SAVE key twice (according to

paragraph 9.1).

 If

the

Insulation

resistance

is

higher

than R

MAX

(see Table2),

the instrument emits a
double beep at the end
of the test indicating
the positive outcome
of the test
and displays
one screen similar to the
screen to the right.

M

05.06.01

Maximum resistance value
which can be measured
(999

is displayed if a

rated voltage of 500V was
selected, see Table2).

> 999

M

523V 15s

MAN 500V

The symbol ">" means that
the resistance value is
higher than R

MAX

.

Test duration

FUNC VNOM

The displayed result can be stored by pressing the SAVE key twice (refer to

paragraph 9.1).