Amprobe, Dmiii multitest, En-77 – Amprobe DMIII-Multitest Power-Quality-Recorder User Manual

Page 79: Power quality function

Advertising
background image

AMPROBE

DMIII MULTITEST

EN-77

14.1.2. POWER QUALITY function

VOLTAGE MEASUREMENT

– (AUTORANGE)

Range [V]

Resolution [V]

Accuracy

Input Impedance

15

310V

0.2V

(0.5% Reading+2digit)

300k

(Phase-Neutral)

300k

(Phase-Phase)

310

600V

0.4V

VOLTAGE SAG AND SURGE DETECTION

–(MANUAL RANGE)

Range [V]

Resolution

(Voltage)

Resolution

(Time)

Accuracy

(Voltage)

Accuracy (rif. 50Hz)

(Time)

Input Impedance

15

310V

0.2V

10ms (½ period)

(1.0% Reading+2digit)

10ms (½ period)

300k

(Phase-Neutral)

300k

(Phase-Phase)

30

600V

0.4V

CURRENT MEASUREMENT

– STD & FlexEXTclamps

Range [V]

Resolution [mV]

Accuracy

Input Impedance

Overload Protection

0.005

0.26V

0.1

(0.5% Reading+2digit)

200k

5V

0.26

1V

0.4

(*): Example: with a 1000A/1V full scale clamp , the instrument detect only current higher than 5A

CURRENT MEASUREMENT

– FlexINT clamp – 1000A Range

Current Range

Input Voltage Range

Resolution

Accuracy

Input Impedance

Overload

Protection

5.00

20.00A

425

V

1.7mV

0.850

V

(4.0%rdg + 8.5

V)

9.166k

5V

20.00

99.99A

1.7mV

8.499mV

0.850

V

(1.0% rdg + 8.5

V)

100.0

999.9A

8.5mV

84.99mV

8.5

V

(1.0% rdg + 85

V)


CURRENT MEASUREMENT

– FlexINT clamp – 3000A Range

Current Range

Input Voltage Range

Resolution

Accuracy

Input Impedance

Overload

Protection

15.00

99.99A

1.27mV

8.499mV

0.850

V

(1.0% rdg + 8.5

V)

9.7k

5V

100.0

270.0A

8.5mV

22.75mV

8.5

V

(1.0% rdg + 42.5uV

270.0

999.9A

22.75mV

84.99mV

8.5

V

(1.0% rdg + 85uV)

1.00

3.00kA

85mV

255mV

850

V

(0.5% rdg + 8.5mV)


POWER MEASUREMENT

– (AUTORANGE)

Quantity

Range

Accuracy

Resolution

ACTIVE POWER

0

999.9W

1

999.9kW

1

999.9MW

1000

9999MW

(1.0%Reading+2digit)

0.1W

0.1kW

0.1MW

1MW

REACTIVE POWER

0

999.9VAR

1

999.9kVAR

1

999.9MVAR

1000

9999MVAR

0.1VAR

0.1kVAR

0.1MVAR

1MVAR

APPARENT POWER

0

999.9VA,

1

999.9kVA,

1

999.9MVA

1000

9999MVA

0.1VA

0.1kVA

0.1MVA

1MVA

ACTIVE ENERGY
(Classe2 EN61036)

0

999.9Wh,

1

999.9kWh,

1

999.9MWh

1000

9999MWh

0.1Wh

0.1kWh

0.1MWh

1MWh

REACTIVE ENERGY
(Classe3 IEC1268)

0

999.9VARh,

1

999.9kVARh,

1

999.9MVARh

1000

9999MVARh

0.1VARh

0.1kVARh

0.1MVARh

1MVARh

Cos

MEASUREMENT

Cos

Resolution

Accuracy [°]

1.00

– 0.80

0.01

0.6

0.80 - 0.50

0.7

0.50

– 0.20

1.0

VOLTANGE AND CURRENT HARMONICS MEASUREMENT

Range

Accuracy

Resolution

DC

– 25H

(5% + 2 digit)

0.1V / 0.1A

26H

– 33H

(10% + 2 digit)

34H

– 49H

(15% + 2 digit)

Harmonics values are null under fixed threshold:

- DC: its values is null if it is < 2%of Fundamental or is <2% of Full Scale clamp

- 1

st

Current Harmonic: its values is null if it is < 0.2% Full Scale clamp

- 2

nd

49

th

: its values is null if it is < 0.5% of fundamental or is < 0.1% of Full Scale clamp

Advertising