Amprobe, Attention, Dmiii multitest – Amprobe DMIII-Multitest Power-Quality-Recorder User Manual

Page 32: En-30

Advertising
background image

AMPROBE

DMIII MULTITEST

EN-30

6.4.

GROUND TEST: SOIL RESISTANCE AND RESISTIVITY MEASUREMENTS

Turn the rotary knob to the GROUND TEST position.


The F1 key permits to select one of the following measuring modes (which
can be shown cyclically when pressing the key):

 Mode "2-W" (the instrument measures the resistance between 2 points).
 Mode "3-W" (the instrument measures the resistance using two auxiliary

earth rods).

 Mode "

" (the instrument measures the ground resistivity).

ATTENTION

Never disconnect the test leads from the circuit under test when the message
"MEASURING" is displayed


6.4.1. Measurement procedure and results of "2-W"and "3-W" mode

1. Select "2-W" or "3-W" Ground measurement mode by means of the F1 key.
2. Connect the Black, Red, Blue and Yellow cables to the corresponding input terminals

of the instrument T1, T2, T3, T4 (see possible connections in the following pictures).

1

3
N

T1 T2 T3 T4

I1 I2 I3

(V1) (V2) (V3)

( COM)

Connection for 3 point Earth resistance

measurement

1

1

3

3

N

N

Transf

T1 T2 T3 T4

I1 I2 I3

(V1) (V2) (V3)

(COM)

Connection for 2 point Earth Resistance

measurement

1

3
N

T1 T2 T3 T4

I1 I2 I3

(V1) (V2) (V3)

(COM)

Connection for measuring the resistance between an extraneous conductive part and the earth system

3. Press the START key. The instrument starts the test.

START

STOP

Advertising