The chosen configuration is the following (for POWER QUALITY function)

 ANALYZER CONFIG:

Frequency:

60Hz

Full scale of the clamps:

1000A

Transforming ratio of voltmetric transformers:

1

Type of electrical equipment:

4 wires

Password:

enabled

 RECORDER CONFIG:

Start:

Manual (the recording is started

at 00 sec mark on clock after pressing

the START/STOP key)

Stop:

Manual

Integration period:

15min

Recording of harmonics:

ON

Recording of Sag and Surge:

ON

Voltage Reference for Sag and Surge detection:

110V

Upper Limit for Sag and Surge detection:

6%

Lower Limit for Sag and Surge detection:

10%

Selected voltages:

V1, V2, V3

Selected voltage harmonics:

Thd, 01, 03, 05, 07

Selected currents:

I1, I2, I3, IN

Selected current harmonics:

Thd, 01, 03, 05, 07

CO-GENERATION:

OFF

Powers, Pf and cos

selected:

Pt, P1, P2, P3

Qti, Q1i, Q2i, Q3i

Qtc, Q1c, Q2c, Q3c

St, S1, S2, S3

Pft, Pf1, Pf2, Pf3

dpft, dpf1, dpf2, dpf3

Energies:

Eat, Ea1, Ea2, Ea3

Erit, Eri1, Eri2, Eri3

Erct, Erc1, Erc2, Erc3

Est, Es1, Es2, Es3


If the user changed the instrument’s settings can quickly resume the above configuration
using the RESET option (see paragraph 5.5).

By pressing START/STOP the recording of the selected parameters is started according to
the settings made in the MENU (see paragraphs 7.1 and 7.2). The rotary switch position
doesn’t affect the recording setting.

The instrument will Start the recording when the Time reach hh:mm:00sec (MAN mode) or
when the START Date and Time (see paragraphs 7.1 and 7.2) will be reached. Before of
that the instrument will display the message “

Please wait…

”.


As the default value of the integration periods is set at 15 minutes the instrument will store
data in the temporary memory for 15 minutes. Afterwards the instrument will elaborate the
results saved in the temporary memory and will save the result of this elaboration (min,
avg, and max values) in the definitive memory. Therefore, if an integration period of 15
minutes has been set, the recording will continue for about 15 minutes before producing a
series of recorded values. If the recording is interrupted before the selected integration
period has completely elapsed the data stored in the temporary memory will not be