Amprobe, Dmiii multitest, En-96 – Amprobe DMIII-Multitest Power-Quality-Recorder User Manual

Page 98: Conventions on powers and power factors, Where

Advertising
background image

AMPROBE

DMIII MULTITEST

EN-96

16.8.1. Conventions on powers and power factors

As for the recognition of the type of reactive power, of the type of power factor and of the
direction of the active power, the below conventions must be applied. The stated angles
are those of phase-displacement of the current compared to the voltage (for example, in
the first panel the current is in advance from 0° to 90° compared to the voltage):

Equipment under test = Inductive Generator

Equipment under test = Capacitive Load

90°






180°

P+ = 0
Pfc+ = -1
Pfi+ = -1

Qc+ = 0
Qi+ = 0

P - = P

Pfc - = -1

Pfi - = Pf

Qc- = 0

Qi - = Q


P+ = P
Pfc+ = Pf
Pfi+ = -1
Qc+ = Q
Qi+ = 0

P - = 0
Pfc - = -1
Pfi - = -1
Qc- = 0
Qi - = 0













P+ = 0
Pfc+ = -1
Pfi+ = -1

Qc+ = 0
Qi+ = 0

P - = P
Pfc - = Pf

Pfi - = -1

Qc- = Q

Qi - = 0


P+ = P
Pfc+ = -1
Pfi+ = Pf
Qc+ = 0
Qi+ = Q

P - = 0
Pfc - = -1
Pfi - = -1
Qc- = 0
Qi - = 0







270°

Equipment under test = Capacitive Generator

Equipment under test = Inductive Load


where:

Symbol

Significance

Remarks

P+

Value of the active power +

Positive parameter

(user)

Pfc+

Capacitive power factor +

Pfi+

Inductive power factor +

Qc+

Value of the capacitive reactive power +

Qi+

Value of the inductive reactive power +

P-

Value of the active power -

Negative parameter

(generator)

Pfc-

Capacitive power factor -

Pfi-

Inductive power factor -

Qc-

Value of the capacitive reactive power -

Qi-

Value of the inductive reactive power -

Value

Significance

P

The active power (positive or negative) is defined in the panel and therefore acquires the value
of the active power in that moment.

Q

The reactive power (inductive or capacitive, positive or negative) is defined in the panel and
therefore acquires the value of the reactive power in that moment.

Pf

The power factor (inductive or capacitive, positive or negative) is defined in the panel and
therefore acquires the value of the power factor in that moment.

0

The active power (positive or negative) or the reactive power (inductive or capacitive, positive
or negative) is NOT defined in the panel and therefore acquires a null value.

-1

The power factor (inductive or capacitive, positive or negative) is NOT defined in the panel.





Advertising