background image

AMPROBE

DMIII MULTITEST

EN-26

The displayed result can be stored by pressing the SAVE key twice (refer to

paragraph 9.1).

6.3.

:

PHASE SEQUENCE INDICATOR

Turn the rotary knob to the

position.



6.3.1. Measurement procedure and results of "

" mode


1. Connect the Black, Red and Blue connectors of the split cables to their

corresponding input terminals of the instrument T1, T2, T3.

L1

L3

T1 T2 T3 T4

I1 I2 I3

(V1) ( V2) (V3)

(COM)

Instrument connection for Phase Sequence Detection in a 400V three-phase system

2. Press the START key to execute a test.


 At the end of the test

the instrument emits a
double

beep

indicating that the test
has

correctly

terminated

and

displays the values to
the right.

LOOP

05.06.01

Phase Sequence OK

123

FRQ=60.0HZ V1-2=115V

V2-3=113V V3-1=114V

OK

Value of the Phase to Phase
Voltage

Working mode


This result can be stored pressing the SAVE key twice (refer to paragraph 9.1).