Series 7400 Single Phase 1+N UPS









The circuit block annotated ‘Static Switch’ in figure 2 contains an

electronically controlled switching circuit, which enables the critical

load to be connected either to the Inverter output or to a Bypass
power source via the ‘static bypass line’. Normally, the load is

connected to the inverter; but in the event of a UPS overload, or

inverter failure, it is automatically transferred to the static bypass
line due to static switch action. Note that the Bypass supply should

be in normal condition and enabled.

To provide a clean (no-break) load transfer between the inverter
output and static bypass line, the inverter output and bypass supply

must be fully synchronised during normal operating conditions.

This is achieved through the inverter control electronics which
make the inverter frequency track that of the static bypass supply -

provided that the bypass remains within an acceptable frequency

window. The synchronising window is pre-selected to 2% of

nominal frequency, giving an acceptable frequency window of
±1Hz.

A warning message [INVERTER UNSYNCHRONIZED] is displayed
on the operator control panel when the inverter and bypass

supplies are not synchronized.


A second, manually controlled, ‘Maintenance bypass’ supply is also

incorporated into the UPS design. Its purpose it to enable the

critical load to be powered from the mains (bypass) supply while

the UPS is shut down for maintenance or troubleshooting.

Note:- The load is unprotected against mains power supply aberrations or
failure when it is connected to either the static bypass or maintenance bypass
supply.

Figure 2: Series 7400 UPS Isolator configurations

1.2.3 Bypass Supplies

RECTIFIER

STATIC

SWITCH

INVERTER

BATTERY

Bypass
Supply

Mains
Supply

UPS
Output
Supply

B a t t e r y
B r e a k e r

O u t p u t

Isolator

I n p u t

Isolator

M a i n t e n a n c e B y p a s s
Isolator

M a i n t e n a n c e B y p a s s L i n e

S t a t i c B y p a s s L i n e

B y p a s s I s o l a t o r

A. BLOCK SCHEMATIC FOR 230V OUTPUT 1PH. UPS SYSTEM

RECTIFIER

STATIC

SWITCH

INVERTER

BATTERY

Bypass
Supply

Mains
Supply

UPS
Output
Supply

B a t t e r y
B r e a k e r

B a t t e r y
B r e a k e r

O u t p u t

Isolator

I n p u t

Isolator

M a i n t e n a n c e B y p a s s L i n e

S t a t i c B y p a s s L i n e

M a i n t e n a n c e B y p a s s
Isolator

B y p a s s
Isolator

B. BLOCK SCHEMATIC FOR 110V OUTPUT 1PH. UPS SYSTEM