Series 7400 Single Phase 1+N UPS

How to turn ON the System from a Shut down condition

(Complete this actions on one module at a time)

This procedure should be followed when turning on the one-plus-one system from a

fully powered down condition - i.e. where the load is not being initially supplied through

the internal Maintenance Bypass supply.

Step Action

Response

1.

Close the module’s Output Isolator
and check that the UPS input mains

supply (and bypass supply if

separate) is turned on externally.

2.

Close the input Isolator (and Static

Bypass Isolator, if separate).














3.

Wait 20 seconds then close the

battery circuit breaker: This is

located inside the battery cabinet (if

used) or is otherwise located
adjacent to the battery racks

4.

Press the battery metering selector
switch [B].





Mimic panel LEDs LS1 LS3 and LS5

should illuminate immediately, to
indicate that the load is being supplied
through the static bypass line

.


(Note: In a Redundant Module system LS5 will
not illuminate on the second module to be
started as its static bypass line is inhibited).


The inverter should start automatically

once the DC Busbar reaches its

working voltage (after about 30
seconds), and when this occurs LS4

(inverter OK) will illuminate followed by

LS6 (load on inverter).

(Note: In a Non-Redundant module system
LS6 will not illuminate on the first module to
be started until you reach this point in starting
the second module.)

Note that LS5 will extinguish when LS6
illuminates.


Mimic panel LED LS2 should illuminate

and LS7 (alarm) should extinguish.


The display should indicate a positive (+)
battery charging current.