10

Series 7400 Single Phase 1+N UPS







The operator control panel is divided into three functional areas;

‘Mimic indications’, Control switches’, and ‘LCD display panel’.


Mimic Indications
Six LEDs are mounted on a single line

diagram to represent the various UPS

power paths. These LEDs, which are

annotated in figure7, show the current UPS
operational status and should be

interpreted as detailed below.


LSI - Input supply OK / Rectifier operative:

This led illuminates when the input isolator

(I1) is closed, the input supply is within 20%
of nominal voltage, and the rectifier is

operative.

LS2 - Battery volts OK:
This led illuminates when the battery circuit

breaker is closed and the battery voltage is

within the UPS operating range - 320V-
432V nominal. (330V - 445V* nominal for

the 80 to 125 kVA Models).


LS3 - Bypass supply OK:

This led illuminates when the static bypass

supply in within 10% of its nominal voltage

and the static bypass isolator is closed.

LS4 - Inverter-output OK:

This led illuminates when the inverter is
operating and its output is within a preset

acceptable voltage window.

Uninterruptible Power System

=

=

ALARM

MEASUREMENTS

INVERTER

EMERGENCY

Vo

f

I o

B

ON

OFF

((•))

Figure 6: Operator Control Panel

1.2.8 Operator Control

Panel

Uninterruptible Power System

=

=

LS1

LS2

LS4

LS6

LS3

LS5

Figure 7: Mimic Panel

* - In case of battery on boost, this voltage can go upto 475V.