1 alarm outputs, 2 remote control inputs – Emerson 7400 User Manual

Page 49

Advertising
background image

40

Series 7400 Single Phase 1+N UPS

4.3 Output Interface (Remote Alarms) Board (100215120007 & 100215120002)


Two remote alarm boards, shown in figure 23 & 24, similar in

function and differing only in their connections to the terminal
blocks M1 - M3, enable the alarm signals generated within the UPS

to be connected by means of volt-free changeover relay contacts

to a remote monitoring device.

Note: When using the above contacts for remote alarm annunciation, the power
supply for the remote indicators must be provided from an external power
source. Under no circumstances should the UPS internal low voltage supplies
be used for this purpose.

Both board have facilities to accept two remote control inputs, as

shown in figures 23 and 24. One remote input allows the inverter to

be shut down (transferring the load to the bypass supply) and the
other enables the inverter synchronisation feature to be inhibited.

This facility is valid only for single module. The inverter

synchronisation inhibit feature is most often used if the UPS is
powered from a standby generator when the input mains supply

fails and the generator frequency is unstable.


The external control signals (12V / 24V) should be connected to

terminal block M2 as shown. Once again, the voltage applied to

these terminals must be generated by an external power source

and not taken from the UPS internal low voltage supplies.

4.3.1 Alarm Outputs

4.3.2 Remote Control

Inputs

15
14
13
12
11
10

9
8
7
6
5
4
3
2
1

15
14
13
12
11
10

9
8
7
6
5
4
3
2
1

LOAD ON BYASS

BATTERY ON LOAD

MAINS FAILURE

OVERLOAD

OVER TEMPERATURE

M2

M3

LOW BATTERY

MAINT. BYPASS ENABLED

INVERTER UNSYNCHRONISED

COMMON ALARM

UPS OK

1 2 3

SH1

RELAY

RELAY

M1

SYNCHRO INHIBIT

INVERTER ON/OFF

1 2 3 4 5

Figure 23: Output Interface Board #100215120007

Advertising