1 cable entry, 2 cable rating – Emerson 7400 User Manual

Page 34

Advertising
background image

25

Series 7400 Single Phase 1+N UPS

3.3 Connecting UPS Power Cables

WARNING

Ø Before cabling-up the UPS, ensure that you are aware

of the location and operation of the external isolators
that connect the UPS Input / Bypass supply to the

mains distribution panel.

Ø Check that these supplies are electrically isolated and

post any necessary warning signs to prevent their
inadvertent operation.


Cables can enter the UPS modules and battery cabinet either from

below or through either side. Side entry is made possible by

removing blanking pieces fitted in the side ventilation grills to reveal

the cable entry holes. This cable entry method allows the
equipment to be positioned on a solid floor without the need for

cable trenching and also allows cables to pass from one module to

the other when positioned side-by-side.

When connected as a one-plus-one Non Redundant system, the

UPS modules’ input and output cables must be rated to suit the
supported load rather than the individual module’s power rating.

This is due to the possibility of connecting the full load to the mains

via the Maintenance Bypass line of one module.

In a Redundant system this is unnecessary as each module is

individually rated to support the full load, and the input/output

cables can be sized to suit the modules’ rating according to the
table given below.

NOMINAL CURRENT (AMPS) 1 PH. UPS

INPUT MAINS

BYPASS/ OUTPUT

BATTERY

UPS

RATING

380V

415V

110V

230V

25

40

50

60

80

90

105

125

53

85

106

128

167

190

219

261

49

78

98

117

153

173

199

237

227

364

455

546

727

818

955

1136

109

174

217

261

348

391

457

544

68

110

136

163

216

240

279

331


3.3.1 Cable Entry

3.3.2 Cable Rating

Advertising