Series 7400 Single Phase 1+N UPS


Mimic panel LEDs LS4 and LS6 should
extinguish on both modules and LS5

should illuminate to show that the load

has been transferred to the static

bypass line.

Note: On a redundant system both Inverter
OFF switches (S6) must be operated before
LS5 illuminates but in a non-redundant system
the Inverter OFF switch must be pressed on
one module only before LS5 illuminates.
However, as the load is transferred to the
static bypass, the second module should be
turned OFF also.

Mimic panel LEDs - No change

Mimic panel LED

LS5 should

extinguish on both modules.

All the operator panel led indications

and messages should extinguish as
the mains driven internal power

supplies decay.



















WARNING

The following points will be live within the UPS:

- Bypass supply input terminals

- Maintenance Bypass Isolator switch

- Static Bypass Isolator Switch (if fitted)
- UPS output terminals

How to turn OFF the System but continue to provide

Load power through the Maintenance Bypass

This procedure should be followed if one-plus-one is to be powered-down while

continuing to supply load through the maintenance bypass line. Note that during this

procedure the load will be unprotected against mains supply disturbances once the
inverter(s) has been switched off.

1.

Ensure that LS3 is illuminated on the

mimic panels (indicating that the
static bypass supply is healthy).

2.

Press the Inverter OFF switch (S6) on
both modules





3.

Close the Maintenance Bypass
Isolator on both modules.

4.

Open the Output Isolator on both
modules.

5.

On each module - Open the battery

circuit breaker followed by the input
Isolator (and Static Bypass Isolator if

separate. For 110V systems Static

bypass isolator is mounted in
auxiliary cubicles).

6.

Isolate the UPS input supply from the

mains distribution panel to make the
UPS safe for work to be carried out

internally.

Step Action

Response