Series 7400 Single Phase 1+N UPS

6.

Connect the safety earth and any necessary bonding earth
cables to the copper earth busbar located on the floor of the

equipment below the power connections.

Note:- The earthing and neutral bonding arrangement must be in
accordance with local and national codes of practice.


7.

Connect the battery circuit breaker control cables between

the UPS auxiliary terminal block and battery circuit breaker

controller board as shown in figures 19 & 20.


8.

If an external emergency stop facility is to be used then

remove the link between terminals 4 and 5 of the auxiliary

terminal block and connect the ‘normally closed’ remote stop
circuit between these two terminals.


Note:- Terminals 8 and 9 on the auxiliary terminal block are connected to
a pair of ‘normally closed’ contacts on the UPS emergency stop button
and will go open circuit when the emergency stop pushbutton is pressed.
These terminals can be used to control an external circuit breaker
connected in the UPS input mains supply line to isolate the UPS input
power when the emergency stop button is pressed.


9.

Connect one-plus-one parallel control ribbon cables between

the Parallel Interface boards of both modules. Connect one

ribbon cable between sockets CN1 on one board and CN2 on

the other, and connect the second ribbon cable between the
remaining CN1 and CN2 sockets. Refer figure 10.

10. Maintenance bypass switch auxiliary wires at terminals 10 &

11 should be connected to other module terminals 10 & 11.

MODULE 1

MODULE 2

COMMON BATTERY PANEL

CN2

CN3

CN1

CN2

CN3

CN1

CN2

CN3

CN1

CN2

CN3

CN1

CN2

CN3

CN1

CN2

CN3

CN1

CN2

CN3

CN1

CN2

CN3

CN1

CN2

CN3

CN1

MODULE 1

MODULE 2

Figure 10: Connecting the parallel interface cables.