Emerson 7400 User Manual

Page 65

Advertising
background image

56

Series 7400 Single Phase 1+N UPS










DISPLAY MESSAGE

INTERPRETATION

UPS ON

MAINTENANCE

BYPASS





INVERTER

UNSYNCHRONISED




BATTERY ON LOAD



MAINS FAILURE



LOAD ON BYPASS




This is a status warning that the load is being powered through

the maintenance bypass line and is unprotected from mains

supply abbreviations. Due to the fact that the UPS power

supplies are fed by the input circuit breaker, this message will
disappear if the input isolator is opened (and bypass isolator

opened on a split bypass system) while the load is on

maintenance bypass supply.

This warns that the inverter is not synchronised with the bypass

supply, which is normally due to a problem with the bypass
supply being outside an acceptable frequency window. Do not

switch OFF the inverter when this alarm is active or the load will

experience a 20-millisecond power break.


This is a status warning that the battery is discharging. It

normally accompanies a [MAINS FAILURE] / [BYPASS FAILURE]

or [RECTIFIER OFF OR FAILED] message.

MAINS FAILURE or mains supply out of specified acceptable

range. Do not switch OFF the inverter while this indication is

active or the load will lose its power.

This is a status warning that the load is being powered through

the static bypass line and is unprotected from mains supply
aberrations.