Emerson 7400 User Manual

Page 63

Advertising
background image

54

Series 7400 Single Phase 1+N UPS














** Note that in one-plus-one system configured with a redundant

module, it is possible for one of the two modules to shut down (due
to fault for example) without turning on its static switch. In fact

when in a redundant module configuration a module’s static switch

is disabled whenever its partnering module is on line. Therefore in
the event of a fault you are likely to see LS4, LS5 & LS6 all OFF.

LED

NORMAL

ACTIONS TO BE TAKEN IF ABNORMAL

NUMBER

STATE

LS4






LS5**


LS6**

ON






OFF


ON

If this led is OFF it signifies that the inverter is not
producing its correct output voltage.

Check the following:

a) If [OVERTEMPERATURE] OR [OVERLOAD] alarm

messages are active then (after allowing the

UPS to cool / checking that the load current on

the bypass line is not excessive) press the reset
switch on the UPS Logic Board.

b) Press the Inverter ON pushbutton

c) If the dc busbar is below 320V (330V for 80-125

kVA) then do checks as per LS1 above

d) Check that slide switch I3 is closed on the UPS

Logic Board is closed.

e) If the inverter works OK when mains is available

but not when mains is unavailable then check

the dc power supply fuses.


If the above checks prove unsatisfactory then seek

qualified assistance.

If this led is ON then it signifies that the load has been
transferred to the static bypass supply and the output

circuit breaker is closed. This indication should be

mutually exclusive with LS6 described below - check
out LS6 actions.

If LS4 is also OFF then refer to LS4 checks.
If LS6 is OFF but LS4 is ON then check the following:

a) Ensure that the output isolator is closed then

press the Reset button on the UPS Logic Board.

b) Ensure that slide switch l3 on the Static Switch

Logic Board is in the AUTO position.

If the above checks prove unsatisfactory then seek

qualified assistance.