Series 7400 Single Phase 1+N UPS









IMPORTANT

The Maintenance Bypass Isolator may be operated at any time when the UPS is

powered down to connect / disconnect each load to the raw maintenance bypass

supply if required.


Emergency Stop

The emergency stop pushbutton is located behind a hinged safety shield to prevent
inadvertent operation. When this switch is pressed both modules are electronically

shut down and both battery circuit breakers are tripped. Power is removed from the

critical load, but pressing the emergency stop pushbutton will not remove the

modules’ input mains supply unless an external contactor, controlled via the
emergency stop pushbutton, is fitted in the mains supply line.

How to totally Power down the System

This procedure should be followed only if the one-plus-one AND LOAD are to be

completely powered down.

Step Action

Response

1.

Press the Inverter OFF switch (S6)

on both modules.



2.

Open the battery circuit breaker.


3.

Open the input isolator (and static

bypass isolator also. For 110V
systems Static bypass isolator is

mounted in auxiliary cubicles).

Mimic panel LEDs - LS4 and LS6 should

extinguish and LS5 should illuminate to

show that the load has been transferred
to the static bypass line.

(Note: In a Non- Redundant Module system LS5
and LS6 will also changeover on the second
module)


Mimic panel LEDs LS2 should

extinguish.

All the operator panel led indications and
messages should extinguish as the

mains driven internal power supplies

decay.