4

Series 7400 Single Phase 1+N UPS

Figure 2 illustrates what is known as the “Split Bypass”

configuration. This is the standard configuration for all 1PH Models

In the “Split Bypass” configuration the static bypass line is switched

by a separate isolator to a dedicated ‘Bypass’ power source which

also feeds the maintenance bypass line.

The power switch locations in the various 7400 models are shown

in Figure 3.

With the exception of the maintenance bypass isolator, all the

isolators shown must be closed during normal UPS operation.

Although it cannot be classified as a ‘power’, the reset switch may

be used as a part of the UPS operating procedure. Fitted to the

UPS Logic Board, the reset switch is used by the operator to re-
transfer the load to the inverter following a detected overload or

overtemperature fault.


The battery is connected to the DC Busbar through a circuit

breaker fitted inside the battery Cabinet / Rack or located adjacent
to the batteries where a battery Cabinet / Rack is not used. This

circuit breaker is closed manually, but it contains an undervoltage

release coil which enables it to be tripped from the UPS control

electronics following certain detects for faults. It also has a
magnetic trip facility for overload protection.

1.2.4 UPS Power

Switch
Configuration

1.2.5 Battery Circuit

Breaker