Installation, Four 45° offsets, Zero or two 45° offsets – FireplaceXtrordinair 36 DV EFIII User Manual

Page 20

Advertising
background image

2 0

Installation

(for qualified installers only)

Travis Industries

4040708

1 0 0 - 0 1 1 6 0

Vertical Terminations with 0, 2, or 4 45° Offsets using 6-5/8” Dia. Vent

Use 6-5/8” diameter co-axial vent

A Maximum of Four 45° Elbows May be Used

10' Minimum System Height (with or without offsets)

40' Maximum System Height

12’ 8” Maximum Horizontal Offset

Offset Length

Hor. Offset

Vert. Rise

None

5"

1'

1' Section

1'

1' 7"

2' Section

1' 9"

2' 4"

3' Section

2' 5"

3'

4' Section

3' 2"

3' 8"

Offset
Length

Horizontal
Offset

Vertical

Rise

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor position.

Restrictor

Position # 1

5 feet

10 feet

(min.)

15 feet

20 feet

25 feet

30 feet

0 feet

0 feet

5 feet

12' 8" (max)

5 feet

0 feet

0 feet

5 feet

12' 8" (max)

10 feet

(min.)

15 feet

20 feet

25 feet

30 feet

NOTE:
Restrictor positions are based upon
lab tests. The ideal restrictor position
may vary slightly, especially when the
termination is near the demarkation
line.

Four 45° Offsets

5 feet

10 feet

(min.)

15 feet

20 feet

25 feet

30 feet

0 feet

40' (max)

0 feet

5 feet

12' 8" (max)

5 feet

0 feet

0 feet

Restrictor

Position # 1

Restrictor

Position # 7

10 feet

(min.)

15 feet

20 feet

30 feet

40' (max)

Zero or Two 45° Offsets

5 feet

NOTE:
The maximum offset
lengths, combined, is
four 4' sections.

NOTE:
Restrictor positions are based upon lab tests. The
ideal restrictor position may vary slightly, especially
when the termination is near the demarkation line.

25 feet

10 feet

10 feet

12' 8" (max)

10 feet

NOTE:
The maximum offset lengths,
combined, is four 4' sections.

10 feet

35 feet

35 feet

40' (max)

40' (max)

Restrictor

Position # 7

35 feet