1 accessing a power supply unit, 2 removing the power supply unit, Accessing a power supply unit – FUJITSU M3000 User Manual

Page 143: Removing the power supply unit

Advertising
background image

Chapter 12

Power Supply Unit Replacement

12-3

12.1

Accessing a Power Supply Unit

Because the power supply unit (PSU) does

Section 4.4.1, “FRU Removal and

Replacement (Power supply unit/Fan unit)” on page 4-8

.

For cold replacement, stop the domain and then power off the server. See

Section 4.5.1, “Powering off the Server” on page 4-12

.

Caution –

To ensure that you and bystanders are not exposed to harm and to

prevent damage to the system, observe the ESD safety precautions. See

Section 1.1,

“ESD Precautions” on page 1-1

.

1. From the XSCF Shell prompt, use the replacefru command to disable the

power supply unit to be removed.

The replacefru command is a menu-driven interactive command. The
replacefru

continues operating while the power supply unit is removed.

Afterwards, it performs the power supply unit test. For details, see

Section 4.4.1,

“FRU Removal and Replacement (Power supply unit/Fan unit)” on page 4-8

.

2. Loosen the thumbscrew of the cable management arm that is located on the

right side when you are facing the rear of the server.

3. Pull out the cable management arm while keeping it from coming into contact

with the power supply unit.

12.2

Removing the Power Supply Unit

1. Verify that the CHECK LED of the power supply unit is blinking and the DC

LED is off.

2. Release the lock of the cord clamp (1 in

FIGURE 12-2

).

3. Remove the power cord from the power supply unit (2 in

FIGURE 12-2

).

XSCF> replacefru

Advertising