D.4 power supply conditions, D.4.1 input circuit, Power supply conditions – FUJITSU M3000 User Manual

Page 186: D.4.1, Input circuit

Advertising
background image

D-4

SPARC Enterprise M3000 Server Service Manual • February 2011

On: Indicates that the contact is closed.

Off: Indicates that the contact is open.

Note 1: Use a UPS that can normally supply power from the battery at least 10 to 60 seconds after *BTL is turned on.

Note 2: Use a UPS that can normally supply power from the battery within 2 seconds of a momentary commercial power interruption

even if *ACOFF is not turned on.

D.4

Power Supply Conditions

TABLE D-2

and

TABLE D-3

show the power supply conditions of the UPC interface.

D.4.1

Input Circuit

Limit the signal line chattering period to 1 ms.

*ACOFF

Indicates that a power failure has occurred in the
commercial power supply connected to the UPS.

9

Normal state: Off
Abnormal state: On
(Note 2)

SG

Signal ground

5

ER
(Equipment Ready)

Indicates that the server is operating

1

Do not connect
anything to this pin.

TABLE D-2

Input Power Supply Conditions

Signal name

Input conditions

*BPS/*UALM

No voltage relay contact

*BTL

Contact rating DC 12 V, 10 mA or greater (0.5 A maximum)

*ACOFF

Use of a gold-plated contact or reed relay is recommended.

TABLE D-1

Signal Line Definitions (Continued)

Signal name

Definitions

Pin number

Remarks