Operator panel replacement, 1 operator panel replacement – FUJITSU M5000 User Manual

Page 249

Advertising
background image

15-1

C H A P T E R

15

Operator Panel Replacement

This chapter describes how to remove and install the operator panel. The information
is organized into the following topic:

Section 15.1, “Operator Panel Replacement” on page 15-1

Section 15.2, “Accessing the Operator Panel” on page 15-4

15.1

Operator Panel Replacement

The operator panel is a cold replacement component. This means the entire server
must be powered off and the power cords disconnected to replace the operator panel.

Note –

If you replace the XSCF unit and the operator panel simultaneously, system

will not operate normally. Execute the showhardconf command or the showstatus
command to confirm that the component replaced earlier is operating normally,
before replacing the subsequent FRU.