FS-8700-84_Lutron_eLumen Driver Manual

Page 13 of 36


FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

4.1.9.

System Monitor Command – Serial Number

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name, Scan_Interval,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

Length

Serial_num,

5s,

Serial_num,

0,

rdbc,

LUT_GRF6_0,

serial_no,

1


Data storage in Data Array
Position from offset

Description

0 Serial

number

4.1.10. System

Monitor Command – Area Status

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Scan_Interval, Data_Array_Name,

Data_Array_Offset, Function,

Node_Name,

GRAFIK_command,

Area,

Length

Area_sts_00,

1s,

Area_status,

0,

rdbc,

LUT_GRF6_0,

Area_status,

0,

2

Area_sts_01,

1s,

Area_status,

2,

rdbc,

LUT_GRF6_0,

Area_status,

1,

2


Data storage in Data Array
Position from offset

Description

0

System scene on status

1

Sequence running status


Note: This command stores 2 data values. To prevent overlaps, remember to increment Data_Array_Offset by 2 when referencing the same Data
Array with other Map Descriptors.