FieldServer FS-8700-84 User Manual

Page 31

Advertising
background image

FS-8700-84_Lutron_eLumen Driver Manual

Page 28 of 36


FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

4.1.38.

System Control Commands Containing Parameters: Ramp zone(s) up

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

DA_Lut_Parms,

DA_Lut_Parms_Offset,

Length

Rmp_zones_up,

Lut_triggers,

21,

awt,

LUT_GRF6_0,

ramp_zones_up,

Zone_list,

0,

Zone_pars,

0,

1


DA_Lut_List setup
Position from DA_Lut_List_Offset

Description

0-63

Zone(s) to ramp up


DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset

Description

0

Initial rate step size

1

Repeat rate step size

4.1.39.

System Control Commands Containing Parameters: Ramp zone(s) down

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

DA_Lut_Parms,

DA_Lut_Parms_Offset,

Length

Rmp_zones_up,

Lut_triggers,

22,

awt,

LUT_GRF6_0,

ramp_zones_down,

Zone_list,

0,

Zone_pars,

0,

1


DA_Lut_List setup
Position from DA_Lut_List_Offset

Description

0-63

Zone(s) to ramp down


DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset

Description

0

Initial rate step size

1

Repeat rate step size

Advertising