4.1.31.
System Control Commands containing no Parameters: Enable wallstation(s)
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
GRAFIK_command,
DA_Lut_List,
DA_Lut_List_Offset,
Length
Enable_ws,
Lut_triggers,
14,
awt,
LUT_GRF6_0,
ena_wallstation,
Ctrl_ws_list,
0,
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0
Link number ( 0-11 ) of Station ID 0
1
Station on link ( 0-31 ) of Station ID 0
.. ..
62
Link number ( 0-11 ) of Station ID 31
63
Station on link ( 0-31 ) of Station ID 31
Note: 1 to 32 station ids may be used to enable wallstations. To trigger the command, write the number of station IDs into the Data Array specified
by Data_Array_Name at Data_Array_Offset
4.1.32.
System Control Commands containing no Parameters: Disable wallstation(s)
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
GRAFIK_command,
DA_Lut_List,
DA_Lut_List_Offset,
Length
Disable_ws,
Lut_triggers,
15,
awt,
LUT_GRF6_0,
dis_wallstation,
Ctrl_ws_list,
0,
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0
Link number ( 0-11 ) of Station ID 0
1
Station on link ( 0-31 ) of Station ID 0
.. ..
62
Link number ( 0-11 ) of Station ID 31
63
Station on link ( 0-31 ) of Station ID 31
Note: 1 to 32 station ids may be used to disable wallstations. To trigger the command, write the number of station IDs into the Data Array specified
by Data_Array_Name at Data_Array_Offset.