4.1.36.

System Control Commands Containing Parameters: Toggle zone

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

DA_Lut_Parms,

DA_Lut_Parms_Offset,

Length

Toggle_zone,

Lut_triggers,

19,

awt,

LUT_GRF6_0,

toggle_zone,

Zone_list,

0,

Zone_pars,

0,

1


DA_Lut_List setup
Position from DA_Lut_List_Offset

Description

0-63

Zone(s) to toggle


DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset

Description

0

Fade cycles

4.1.37.

System Control Commands Containing Parameters: Fade zone(s) to level

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

DA_Lut_Parms,

DA_Lut_Parms_Offset,

Length

Fade_to_level,

Lut_triggers,

20,

awt,

LUT_GRF6_0,

fade_zone,

Zone_list,

0,

Zone_pars,

0,

1


DA_Lut_List setup
Position from DA_Lut_List_Offset

Description

0-63

Zone(s) to fade to level


DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset

Description

0

Level to fade to ( 0-127 )

1 Fade

cycles

2 Delay

cycles