4.1.33.
System Control Commands containing no Parameters: Simulate wallstation(s) switch press
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
GRAFIK_command,
DA_Lut_List,
DA_Lut_List_Offset,
Length
Ws_sw_press,
Lut_triggers,
16,
awt,
LUT_GRF6_0,
sim_ws_sw_press,
Sim_sw_list,
0,
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0
Link number ( 0-11 )
1
Station of link ( 0-31 ) of Switch ID 0
2
Switch on station ( 0-31 ) of Switch ID 0
3
Station of link ( 0-31 ) of Switch ID 1
4
Switch on station ( 0-31 ) of Switch ID 1
.. ..
63
Station of link ( 0-31 ) of Switch ID 31
64
Switch on station ( 0-31 ) of Switch ID 31
Note: 1 to 32 switch ids may be used in a single command. To trigger the command, write the number of switch IDs into the Data Array specified
by Data_Array_Name at Data_Array_Offset.