FieldServer FS-8700-84 User Manual

Page 18

Advertising
background image

FS-8700-84_Lutron_eLumen Driver Manual

Page 15 of 36


FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

4.1.13.

System Monitor Command – Request Panel Emergency Status

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Scan_Interval,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

Panel,

Length

Pnl_emerg_sts_00,

1s,

Pnl_emerg_sts,

0,

rdbc,

LUT_GRF6_0,

pnl_emerg_status,

0,

1

Pnl_emerg_sts_511,

1s,

Pnl_emerg_sts,

511,

rdbc,

LUT_GRF6_0,

pnl_emerg_status,

511,

1


Data storage in Data Array
Position from offset

Description

0

Panel emergency status
0 = normal; 1 = override


Note: This command stores 1 data value. To prevent overlaps, remember to increment Data_Array_Offset by 1 when referencing the same Data
Array with other Map Descriptors.

4.1.14.

System Monitor Command – System Variable Value

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Scan_Interval,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

Sys_var,

Length

Sys_var_00,

1s,

Sys_vars,

0,

rdbc,

LUT_GRF6_0,

sys_var_val,

0,

1

Sys_var_01,

1s,

Sys_vars,

1,

rdbc,

LUT_GRF6_0,

sys_var_val,

1,

1


Data storage in Data Array
Position from offset

Description

0

System variable value


Note: This command stores 1 data value. To prevent overlaps, remember to increment Data_Array_Offset by 1 when referencing the same Data
Array with other Map Descriptors.

Advertising